Getting Your Ground Down to Earth
By Donald E. Kimberlin
There it was...the perfect pay station location, at a gas station on the corner of a busy intersection, but off on the corner of the
property so people could drive up to it and make their calls. It was so accessible and visible it should have attracted several times
the average number of local calls. It should have returned its investment in one-third the typical time.
But it didnt. In fact, it was out of order more often than it was in service. No physical damage occurred. No vandalism, no cars
driving into the booth, no floods. It never had a real line outage. Its own advanced electronics never reported a failure to you. You
never found out it failed until someone at the location called to complain.
The electronics kept dying. And every time you replaced them, the new ones went dead. No smoke, no flame, no flash. Just dead.
Well, somebody said it might be lightning, so you bought surge protectors for the power line and phone line, but to no avail.
Somebody said you must have a bad ground, so you hired the oldest, most skilled electrician you knew, and he thoroughly
inspected the power line ground and declared that it fully met the National Electrical Code. He even knew how to use a megger
and confirmed the ground resistance was so low it was almost unreadable. The installation met every safety requirement in the book,
he told you. But the phone still kept dying.
The words the electrician used contain the seed of what is wrong. By making the installation safe for people, he also created an
enormous hazard for solid-state electronics. The reason: the ground those electronics need has to be intimately connected to the
potential of the ground right where the phone booth is, neither back at the buildings power panel nor back at the telephone
exchange.
You suggested driving a ground rod at the booth, and the electrician told you that youd violate the code if you did that. Yes, if you
did that and that alone, you would be violating the code and creating a hazard for people. The white or green wire ground used for
power distribution and safety purposes, if broken and replaced by another path to ground (like your proposed ground rod), could
let the power ground in your equipment rise 115 volts above the ground that people stand on in the booth and shock them just as if
they stuck a hairpin in a light socket.
What the electrician didnt remember from his exam days was the special conditions in the national Electrical Code for
communications equipment. They take the form of footnotes that refer to the use of an alternative earthing electrode. Thats the
fancy name for your ground rod at the isolated booth.
When you read about the alternative earthing electrode, you find that the code simply requires that you bond that rod to the power
ground point back in the building with a No. 6 insulated bonding conductor. It is very large to ensure that it is physically durable
and wont break...or at least will break last. Its size also reduces its inductive reactance to make it rapidly follow changes in the
ground potential.
Changes in the ground potential? But isnt the ground always at ground? Isnt it by definition a potential of 0 volts? Dont we
always rely on it to be an unchanging electrical platform? Well, yes, we do. But the truth is that when a huge amount of current
passes through the earth right beneath us, the ground takes on a very jelly-like electrical consistency for those thousandths of a
second while the current is passing by. For a time shorter than the blink of an eye, the earth we rely on to be so stable simply cannot
stay at 0 volts. A pay station relying on a ground at the other end of a power line that is 50, 85, or 120 feet long to the power panel
is connected to the end of an electrical whipsaw whenever a huge current passes through the earth.
When can this happen? Whenever a lightning bolt strikes anywhere within a mile or so of the pay station. The effect is just like a
huge invisible wave radiating outward for up to a mile, until it dissipates. For that instant, everything in the vicinity is at a different
ground potential than the power safety ground.
Visualize being in a small boat with a rope tied back to the shore. Suddenly, a load of rocks gets dumped in the pond and creates a
6-foot wave. You know at that time the wave will swamp your boat when it pulls the rope tight. It would be better to cut the rope
and try to float on the wave. But a smart sailor knows how to use a sea anchor, a device that works to keep your boat still by
connecting it to the surface near the boat.
Electrical power engineers know the condition well, and they call a similar electrical wave ground potential rise. The sea anchor is
analogous to the alternative earthing electrode, your ground rod at the phone booth. But, because power safety prohibits us from
cutting loose from the shore, the code then requires us to back up the electrode with the bonding conductor.
In fact, in the NEC section formally titled NFPA 78--The National Lightning Code, the alternative earthing electrode is required. If
you dont provide it and someone is hurt in or near your booth, you can be liable for some very large damage costs because you
didnt take prudent measures to protect people against hazards from ground potential rise.
Besides, it just makes good business sense to protect the microelectronics boards in your phone. Whats happening to those
microelectronics? It takes a surgeons microtome and a microscope to see it. Right where the 5-volt Zener diode is on the integrated
circuit chips, a sliced-open chip will reveal a microscopic volcano where the diode used to be. Why? Because one end of that diode
has to be connected to what it calls ground to make the circuit work. The amount of current the diode has to conduct for
millionths of a second when its ground floats to thousands--perhaps only hundreds--of volts from normal is so large that the Zener
diode explodes. All it takes is one hit and your smart pay station never gets a chance to dial you up for its own obituary. It just dies
instantly.
So why didnt this affect pay stations before? Thats easy: the electromechanical devices of the monopoly era, those simple relays
and switches, could take repeated hits before they would fail. The dissipating voltage, if high enough to puncture a relays varnished
cotton and even plastic insulation, simply leaves a pinhole in the insulation, and if the operating voltage of 48 volts is still much lower
than the general insulation value of 600 volts or so, the relay keeps working. In fact, it works until enough pinholes, perhaps
dozens or hundreds of them finally, cause so much insulation loss that the relay gets enough shorted turns that it will not work
anymore. Technicians curious enough to unwind a failed relay often wonder what causes the wires peppered appearance.
For this reason, many experienced installers who put in electromechanical pay phones for years never believed the one lesson they
got in bonding and grounding. It seemed to be a theoretical thing that the teacher just wanted to use for an exam question. They had
many years of practical experience that led them to believe an extra ground was not necessary.
But a ground rod is not forever, either. To do its job, it must be in contact with moist soil. That sets up a constant corrosive action
that eventually forms an insulating layer of corrosion on the surface of the rod, so it loses contact with the soil. An annual
maintenance check using a megger--or the more sensitive devices we now have--can show deterioration of the grounding path.
The Rural Electrification Administration charted the United States years ago to show that the entire country, except for a narrow
strip at the Pacific Ocean, has more than five lightning days a year, enough to put 95 percent of the nation at risk for lightning
damage. (Its a kind of natural tradeoff for earthquakes). But, even at the Pacific shoreline, with only one day of lightning per year,
one lightning bolt nearby can kill your modern microelectronic pay station.
As our good ol boys near Southeast lighting centers say, Youd better get your ground down to earth, son!
Written by Donald E. Kimberlin, principle consultant of Telecommunications Network Architects in Safety Harbor, Florida.
This article is adapted from Vol. 3, No. 1, p. 50.